Basque National Orchestra in Miramon (Donostia/San Sebastián)
Vertical closed-loop geothermal exchange system that supplies renewable thermal energy to a ground source heat pump. The system is complemented by an air source heat pump as auxiliary support.
Characteristics
-
Category
Renovation
-
Promoter
Euskadiko Orkestra, S.A.
-
Geological material
Marls and sandy limestones
-
Heated surface
2.800 m²
-
Thermal production
Ground source heat pump
Air source heat pump as backup -
GIS Power
Heating: 116 kW (41% of peak load)
Cooling: 90 kW (53% of peak load) -
GIS Covered Demand
Heating: 126 MWh/year (75%)
Cooling: 73 MWh/year (89%) -
Geothermal exchange circuit
1.650 m: 11 borehole x 150 m
-
Distribution
2 pipes
-
Issuers
Fan coil units
-
Expected energy savings
187 MWh PE/year (-52%)
-
Commissioning
January 2025