Energigune Cooperative Research Center (Araba)
Geothermal exchange system for the air conditioning of the facilities of the Energigune Cooperative Research Center (CIC), located in the Álava Technology Park, in order for said system to supply a significant part of the building's demand.
Characteristics
-
Category
New construction
-
Promoter
Basque Energy Entity EVE-EEE
-
Geological material
Upper Cretaceous marls and margolimestone
-
Heated surface
5.000m²
-
Thermal production
Bivalent with 2 chillers and biomass boiler.
-
GIS Power
300kW Heating.67% of peak load
280kW Cooling 100% of peak load -
GIS Covered Demand
85% heating: 174MWh/year
100% cooling: 83MWh/year -
Geothermal exchange circuit
4000 m drilling in gardens: 32x125 m
-
Distribution
4 tubes
-
Issuers
Fan-coil and air conditioning
-
Expected energy savings
178MWh/year (49% savings)
-
Commissioning
June 2010