Energigune Cooperative Research Center (Araba)

Geothermal exchange system for the air conditioning of the CIC Energigune facilities, Araba Technology Park, Miñano Vitoria-Gasteiz.

Characteristics

  • Category

    New construction

  • Promoter

    Basque Energy Entity EVE

  • Geological material

    Loams and margolimestone (Upper Cretaceous)

  • Heated surface

    5.000m²

  • Thermal production

    2 Water/Water heat pumps
    1 Biomass Boiler

  • GIS Power

    Heating: 300 kW (67% peak load)
    Cooling: 280 kW (100% peak load)

  • GIS Covered Demand

    Heating: 174 MWh/year (85%)
    Cooling: 83 MWh/year (100%)

  • Geothermal exchange circuit

    Vertical Closed Circuit:
    4,000 m / 32 wells

  • Distribution

    4 tubes

  • Issuers

    Fan-coil and air conditioning

  • Expected energy savings

    178MWh/year (-49%)

  • Commissioning

    June 2010