Social Welfare Building Tetuán (Madrid)

Geothermal exchange system for the air conditioning of the Tetuán Social Welfare building, executed to cover 100% of the thermal demand. Water-water heat pump for heating, cooling and preheating of SHW and high temperature water-water heat pump for final heating of SHW.

Characteristics

  • Category

    New construction

  • Promoter

    Apostolic of the Heart of Jesus

  • Geological material

    Thick arkoses and ocher shales

  • Heated surface

    1.470 m²

  • Thermal production

    Ground source heat pumps

  • GIS Power

    Heating: 124 kW (100 % of peak load)
    Cooling: 110 kW (100 % of peak load)

  • GIS Covered Demand

    Heating: 57 MWh/year (100%)
    SHW: 55 MWh/year (100%)
    Cooling: 78 MWh/year (100%)

  • Geothermal exchange circuit

    1,500 m: 12 boreholes x 125 m

  • Distribution

    2 pipes

  • Issuers

    Underfloor heating and fancoils

  • Expected energy savings

    112 MWh PE/year (-64%)

  • Commissioning

    January 2023