TTT Thermal Treatments, Bergara (Gipuzkoa)

Use of residual heat from furnaces through a geothermal exchange system for process heating and heating at TTT Bergara, maintaining the current heating equipment as support. Treatment oven circuit cooling.

Characteristics

  • Category

    Rehabilitation

  • Promoter

    Tratamientos Térmicos TTT S.A.

  • Geological material

    Loams and margolimestone

  • Heated surface

    2.200 m²

  • Thermal production

    High temperature water-water heat pump. R1234ze. boilers and cooling towers

  • GIS Power

    415 kW heating, 100% peak load
    323 kW cooling, 33% of peak load

  • GIS Covered Demand

    100% heating: 853 MWh/year
    64% cooling: 2,060 MWh/year

  • Geothermal exchange circuit

    2.250m drilling: 15 x 150 m

  • Distribution

    4 tubes

  • Issuers

    Air heaters, radiators, process heating, oven cooling

  • Expected energy savings

    968 MWh EP/year (62% savings)

  • Commissioning

    August 2019